Ipec Units

Chemical scrubbers

Ipec chemical scrubbers remove odour from sewage networks with high efficiency and low chemical consumption. The design combines sufficient contact time, a high recirculation flow and chemical dosing on demand.

Why choose a chemical scrubber?

  • Low chemical consumption: chemicals are dosed on actual need, not continuously
  • A PLC monitors H₂S before and after the scrubber, plus the pH of the liquid and the oxidation-reduction potential (ORP) when bleach is dosed 
  • Handles high loads: at Jeddah South, H₂S peaks up to 500 ppm 
  • Single-stage or two-stage, and can be combined with activated carbon
Jeddahsouth 16

How it works

The foul air flows through a packed bed while liquid is sprayed over the packing from the top of the vessel. A limited air velocity gives sufficient contact time, and a high recirculation flow ensures good contact between the air and the liquid. In a two-stage system, the first stage runs on caustic and removes most of the H₂S. The second stage, with caustic and bleach, polishes the air. Mist eliminators stop droplets from reaching the next stage or the stack.

Technical specifications

very Ipec chemical scrubber is designed for the site and the load. The largest so far, at Jeddah South, treats 300,000 m³/h in four trains of 75,000 m³/h.

Scrubbing liquid Acidic, caustic or oxidising (caustic and bleach)
Configuration Single-stage, two-stage, or scrubber followed by activated carbon
Dosing control PLC-controlled, based on measured H₂S, pH and ORP
Ain Khalid 4 1

References

23 chemical scrubber references in 8 countries since 2003.